Coldstore Refrigeration Systems – Glasgow
Refrigeration Systems – Glasgow
ICE Ltd were instructed to replace two old refrigeration systems serving a pharmaceutical coldstore in Glasgow with new, more efficient and reliable systems.
To serve the coldstore we selected two independent, direct expansion refrigeration systems operating on R407F refrigerant, utilising under ceiling mounted evaporator coolers and fully housed packaged condensing units.
Each installed system is capable of 6.18kw of refrigeration duty, providing a total duty of 12.36kw under the conditions specified.
The two refrigeration systems run together continuously to maintain the desired room temperature of 5 oC.
The two under ceiling evaporator coolers are manufactured by Searle and are each matched to condensing units from the Danfoss Optyma Plus range.
The condensing units are installed on anti vibration Flexi Feet to the side of the coldstore and all refrigeration pipe work is supported using standard insulated pipe clamps.
Drains from each cooler are ran in white plastic pipe to an existing drain within the building.
Control of the systems is via Eliwell controllers within a purpose build control panel containing all breakers, contactors, and run/fault lamps.
For all your refrigeration requirements, contact ICE Ltd by calling 01928 568800 or fill out our online form.